The Elkhart Brass second generation Electric Remote-Controlled Monitor (ERCM) system design enables the use of a single PLC-based control panel to manage monitor and nozzle motor functions as well as serving as an Operator Control Panel (OCP).
Reliable Fire Protection Solutions for Industrial Locations
Our UL listed ERCM system is designed to provide a reliable industrial fire protection solution for Class I Division 2 hazardous (classified) locations. The electric monitor and nozzle are FM approved while the control panel is U.L. Listed.
Basic Panel Features
ERCM Applications
Optional Networked Panel Features
8394-053 Spit-Fire® Monitor
Industrial Electric Remote Controlled Monitor; 120VAC (60 Hz) Synchronous motors; 2,000 gpm (7,570 LPM) max flow rate; 200psi (14 BAR) maximum operating; -45° to +90° (135°) max vertical travel; 347° max horizontal travel; 4.0″ 150# ANSI flange inlet; 3.5″ NHT male outlet; 85 brass with red urethane enamel; suitable Class I Division 2 classified location application, FM Approved, NFPA 70 (NEC) compliant, NEMA 4X (IP66) junction box.


Monitor Control Panel (MCP)
Main Monitor Control Panel; Suitable for Class I Division 2 classified location; Factory configured for 3.2A@240VAC 60 Hz input power; factory configurable for 50 hz; field configurable for 120VAC or 480VAC; networkable; /Alarm Input / Group Response over ethernet network; 304 Stainless Steel NEMA 4x enclosure; UL Listed, complies with NFPA 70 (NEC).
- Optional 304 and 316 Stainless Steel NEMA 4x Enclosure or painted carbon steel NEMA 4 Enclosure
- Optional gland plate
- Optional auxiliary device controls

Networked Monitor Control Panel (NMCP)
Optional Networked Monitor Control Panel; Suitable for Class I Division II classified location; 6.3A/3.2A @120/240VAC 50/60 Hz; networkable; Alarm Input / Group Response over ethernet network; 304 Stainless Steel NEMA 4x enclosure; UL Listed, complies with NFPA 70 (NEC).
- Optional Hazardous Location rated (Class I Division 2)
- Optional 304 and 316 Stainless Steel NEMA 4x Enclosure or painted carbon steel NEMA 4 Enclosure
- Optional gland plate
- Optional Single-Mode and/or Multi-Mode Fiber communication connections
- Optional auxiliary device controls

Hardwired Operator Control Panel
Optional Hardwired Operator Control Panel (OCP); Power derived from MMCP; 304 Stainless Steel NEMA 4x Enclosure; UL Listed, complies with NFPA 70 (NEC).
- Optional Hazardous Location rated (Class I Division 2)
- Optional 316 Stainless Steel NEMA 4x Enclosure or painted carbon steel NEMA 4 Enclosure
- Optional gland plate
- Optional auxiliary device controls

Networked Operator Control Panel (NOCP)
- Optional Networked Operator Control Panel (OCP); Power derived from MMCP; 304 Stainless Steel NEMA 4x Enclosure; UL Listed, complies with NFPA 70 (NEC).
- Optional Hazardous Location rated (Class I Division 2)
- Optional 316 Stainless Steel NEMA 4x Enclosure or painted carbon steel NEMA 4 Enclosure
- Optional gland plate
- Optional auxiliary device controls
- Optional Single-Mode and/or Multi-Mode Fiber communication connections

GEN-II XT (eXtreme Temperature) Panels available with higher temperature range


Optional RF Control
Optional RF control enables portable Radio Frequency (RF) control; 1000 feet (305 m) RF control range; networkable with up to 24 monitors per network system. Handheld options available.
- Custom control buttons and switches are availableDiv. 2, Groups C and D, T5 Class II, Div. 2 Groups E, F, and G, Class III:T4


Optional Remote Operator Control Console
Provides control for up to 64 Monitors. Intuitive touch screen interface, providing all Operator Monitor Control Panel functions, advanced monitor configuration, and troubleshooting functions; UL Listed; painted carbon steel enclosure.
- 2.1A Input Power @ 100-120VAC; 1.0A Input Power @ 220-240VAC
- Choice of wall-mount, free-standing console, or desktop (Consolet) Enclosures
- Optional Single-Mode and/or Multi-Mode Fiber communication connections
- Optional EWON device (for remote system access for troubleshooting and support)

Optional Motor Operated Valve (MOV)
- 4.0″ Electric Butterfly Valve
- Can be used on remote controlled monitor systems
- Temperature range: -40 to 149°F; Stainless Steel valve with EPDM seat; 120-240VAC 50/60 Hz., 1-phase operating power; NEMA 4, 4x and 6, IP66/68; operating pressure – 150 PSI
- FM Approved: Class I Zone 1; AEx/Ex de IIB T5: Acceptable for Class I, Div. 2, Groups C and D, T5 Class II, Div. 2 Groups E, F, and G, Class III:T4


Customizable Configurations
Elkhart Brass has a long history of providing customizable, configurable product solutions to its customers. Fire protection systems throughout the world rely on our experience to not only listen to your needs, but deliver top-quality, manufactured products designed to work better.
Have it Your Way
| File | Summary | File Type | Link |
|---|---|---|---|
| 8394053 Monitor and Nozzle |
Monitor Model #8394-053 |
||
| 8394053 Monitor Parts Drawing | |||
| GEN II-Networked Control Panel – Non Hazardous | |||
| Gen II-Networked Control Panel – NON HAZARDOUS | |||
| Manual Hardwired Monitor Control Panel |
Hardwired Monitor Control Panel Model #81471121 and similar panels. (EB #98386200) |
||
| Monitor Motor Control Panel |
| File | Summary | File Type | Link |
|---|---|---|---|
| HMI Manual 98559000 |
HMI Remote Control Console(EB #98559000) |
||
| Manual – Networked MCP |
Model #81471127, 81471128, and similar panels. Networked Monitor Control Panel (EB #98606200) |
||
| Manual Electric Actuated Butterfly Valves |
Model #70117000, 70117200, and 70133000 Electric Actuated Butterfly Valves (EB #98378000) |
||
| Manual Networked RF |
Networked RF Manual Model #81520366, 81520370, 81520371 (EB #98386300) |
||
| The Networked RF Manual 98386300 | |||
| Water Valve Wiring Instructions for Industrial System Control Panels |
Model #81471121, 81471127, 81471128, and similar panels. |
docx |
| File | Summary | File Type | Link |
|---|---|---|---|
| Data Sheet – Industrial EXM2 | |||
| Data Sheet – Industrial Valve |
Industrial Electric Butterfly Valve |
||
| Datasheet – FM/UL ERCM – 24359050 Networked OCP |
FM/UL Networked OCP |
||
| Datasheet – FM/UL ERCM – 8147112 Networked MCP (Non-Hazardous) |
FM/UL Networked OCP |
||
| Datasheet – FM/UL ERCM – 81471121 Hardwired MCP |
FM/UL Hardwired OCP |
||
| Datasheet – FM/UL ERCM – 81471128 Networked MCP |
FM/UL Networked MCP |
||
| Datasheet – Industrial ERCM – Remote Control Monitor System |
FM/UL ERCM – 08394053 |
||
| Datasheet – Industrial ERCM – Washdown |
Washdown |
||
| FM/UL ERCM – 24359051 Hardwired OCP |
FM/UL Hardwired OCP |
| File | Summary | File Type | Link |
|---|---|---|---|
| Industrial Fire Protection Redefined |