The Elkhart Brass ATEX and IECEX certified Remote-Controlled Fire Protection System is designed to provide a reliable industrial fire protection solution for explosive atmosphere applications.
Basic Panel Features
Optional Networked Panel Features
8394-159 Spit-Fire® Monitor Electric Remote Controlled Monitor
220-240VAC (50/60 Hz) Synchronous motors; 2,000 gpm (7,570 LPM) max flow rate; 200 psi (14 BAR) maximum operating pressure; -45 to +90 (135) max vertical travel; 347 max horizontal travel; 4.0″ 150# ANSI flange inlet; 3.5″ NHT male outlet; 85 brass with red urethane enamel; suitable for ATEX Zone 1, Zone 2, Zone 21, Zone 22 and IECEx Zone 1, Zone 2, Zone 21, Zone 22; ATEX and IECEx certified, red paint finish.



SM-1250BE-HL ATEX Nozzle
220-240VAC (50/60 Hz) pattern control synchronous motor; 75 psi (5.17 BAR); 3.5″ NH female base constant flow; 230 ft (70m) effective reach; straight stream; narrow fog (30) and wide fog (90); 350 to 1250 gpm (1,330 to 4,750 LPM) flow rate; brass; suitable for ATEX Zone 1, Zone 2, Zone 21, Zone 22 and IECEx Zone 1, Zone 2, Zone 21, Zone 22 explosive atmospheres; ATEX and IECEx certified, NFPA 70 (NEC) compliant.



SM-2000BE-HL ATEX Nozzle
220-240VAC (50/60Hz) pattern control synchronous motor; 75 psi (5.17 BAR); 3.5″ NH female base constant flow; 320 ft (98m) effective reach; straight stream; narrow fog (30) and wide fog (90); 500 to 2000 gpm (1,900 to 7,600 LPM) flow rate; brass; suitable for ATEX Zone 1, Zone 2, Zone 21, Zone 22 and IECEx Zone 1, Zone 2, Zone 21, Zone 22 explosive atmospheres; ATEX and IECEx certified, NFPA 70 (NEC) compliant.



Standard Panel Local Control Panel
Monitor motor and operator control panel with controls for basic monitor function and water valve operation; suitable for ATEX Zone 1, Zone 2, Zone 21, Zone 22 and IECEx Zone 1, Zone 2, Zone 21, Zone 22; explosive atmospheres; 240VAC 50/60 Hz input voltage; Ex d flameproof enclosure joined with Ex e increased safety enclosure; gland plate included.

Networked Panel Local Control Panel
- Optional Single-Mode and/or Multi-Mode Fiber communication connections
- Optional RF control
- Optional Remote Operator Control Console with Touch Screen



Optional Remote Operator Control Console
Provides Control for up to 64 Monitors. Intuitive touchscreen interface, providing all Monitor Control Panel functions, advanced monitor configuration, and troubleshooting functions; ; UL Listed; painted carbon steel enclosure.
- 2.1A Input Power @ 100-120VAC; 1.0A Input Power @ 220-240VAC
- Choice of wall-mount, free-standing console, or desktop (Consolette) enclosuresOptional Single-Mode and/or Multi-Mode Fiber communication connections
- Optional EWON device (for Elkhart Brass remote system access for troubleshooting and support)

Motor Operated Valve (MOV)
Optional Electric Actuated Butterfly Valve
- 4.0″ Electric Butterfly Valve
- Can be used on remote-controlled monitor systems
- Temperature range: -40 to 149°F; Stainless Steel valve with EPDM seat; 120-240VAC 50/60 Hz., 1-phase operating power; NEMA 4, 4x and 6, IP66/68; operating pressure – 150 PSI
- FM Approved: Class I Zone 1; AEx/Ex de IIB T5: Acceptable for Class I, Div. 2, Groups C and D, T5 Class II, Div. 2 Groups E, F, and G, Class III:T4

Videos
Customizable Configurations
Elkhart Brass has a long history of providing customizable, configurable product solutions to its customers. Fire protection systems throughout the world rely on our experience to not only listen to your needs, but deliver top-quality, manufactured products designed to work better.
Have it Your Way
| File | Summary | File Type | Link |
|---|---|---|---|
| 8394159 Electric Monitor with Nozzle |
Reference Dimensions |
||
| Drawing |
Model #81471125 ATEX-IECEx Networked Monitor Control Panel |
||
| Drawing |
Model #81471124 ATEX-IECEx Standard Monitor Control Panel |
| File | Summary | File Type | Link |
|---|---|---|---|
| ATEX Monitor Manual 08394159 | |||
| ATEX Networked Panel Manual 81471125 | |||
| ATEX Standard Panel Manual 81471124 | |||
| Spitfire Monitor Travel Limit Configuration (EB #39073053) |
Monitor Model #8394-053 ERCM Travel and Stop Screw Drawing |
||
| X-Stream – ATEX Industrial Electric Nozzle Manual |
| File | Summary | File Type | Link |
|---|---|---|---|
| Datasheet ATEX ERCM – 08394159 |
ATEX ERCM |
||
| Datasheet ATEX ERCM – 03783046 Nozzle |
SM-1250BE-HL ATEX |
||
| Datasheet ATEX ERCM MOV |
Motor Operated Valve |
||
| Datasheet ATEX ERCM RF Control |
RF Control |
||
| Datasheet ATEX/IECEx ERCM – 81471124X |
ATEX Standard MCP |
||
| Datasheet ATEX/IECEx ERCM – 81471125 |
ATEX Network MCP |
||
| Datasheet ATEX/IECEx ERCM – 03995046 Nozzle |
SM-2000BE-HL ATEX Nozzle |
||
| Datasheet ATEX/IECEx ERCM Console |
Control Room Console |
||
| EU Declaration of Conformity |
Issued by Elkhart Brass |
||
| EU Declaration of Conformity |
CE Certificate for HMI |
||
| EU Type Examination Certificate for the Spitfire Monitor System |
CML 19ATEX3446X Issue 4 |
||
| IECEx Certificate of Conformity -Electric Spit-Fire Monitor System |
ICECx CML 19.0162X Issue 4 |
||
| IECEX Declaration of Conformity |
Issued by Elkhart Brass |
||
| IECEx Quality Assessment Report Summary |
GB/CML/QAR20.0030/02 |
||
| Quality Assurance Notification |
CML ATEXQ13749 Issue 1 |
| File | Summary | File Type | Link |
|---|---|---|---|
| ATEX Brochure |